Wire Size Calculator
NEC 2023 Table 310.16 ampacity check plus voltage-drop check using the K-method (Mike Holt / IAEI). Returns the smallest copper or aluminum conductor that satisfies both.
Calculation results
Recommended size
Actual voltage drop
Adjusted current
Constraint
Voltage drop uses the K-method with K = 12.9 (Cu) / 21.2 (Al) at 75 °C. Three-phase uses the line-line factor √3 (assumes power factor = 1).
Understanding the formula
Two checks every wire must pass: it must carry the load current without overheating (ampacity, NEC Table 310.16) and it must deliver the load voltage with acceptable drop along the run (voltage drop, NEC informative appendix). The calculator runs both and returns the bigger of the two.
Voltage drop — K-method
Three-phase: VD = (√3 × K × I × D) / CM
K is the resistance constant in ohm·circular-mils per foot at 75 °C operating temperature: 12.9 for copper and 21.2 for aluminum / copper-clad aluminum. CM is the conductor circular-mils area. D is the one-way distance — the formula factor (2 for single-phase, √3 for three-phase) handles the geometry. The K-method assumes power factor = 1.
Continuous loads
NEC 210.19(A)(1)(a) and 215.2(A)(1)(a): a continuous load (≥ 3 hours at full load) requires the wire and the breaker to be sized for 1.25 × the load. The calculator multiplies the load by 1.25 when you mark it continuous.
Voltage drop limits
- Branch — 3 %: NEC 210.19(A)(1) Informational Note 4 — recommendation, not enforceable.
- Feeder + branch — 5 %: NEC 215.2(A)(1)(b) Informational Note 2 — combined feeder + branch.
- NEC 647.4(D): 1.5 % branch / 2.5 % combined for sensitive electronics — mandatory.
- NEC 695.7: stricter limits for fire-pump branches — mandatory.
Worked example
30 A continuous EV charger, 80 ft one-way, 240 V single-phase, copper, 75 °C, 3 % limit:
- I_adj = 30 × 1.25 = 37.5 A
- Ampacity at 75 °C: smallest Cu with ≥ 37.5 A is #8 (50 A)
- VD limit = 240 × 3 % = 7.2 V; CM_min = (2 × 12.9 × 37.5 × 80) / 7.2 = 10,750 CM. Smallest AWG ≥ 10,750 CM is #8 (16,510 CM)
- Recommend #8 AWG copper; actual VD = (2 × 12.9 × 37.5 × 80) / 16,510 = 4.69 V (1.95 %)
When to use this calculator
Pre-flight check before pulling wire on residential and light-commercial circuits: dedicated appliance branches, EV chargers, well pumps, sub-panels, sub-ground feeders to outbuildings, lighting feeders.
The calculator does not handle:
- Ambient-temperature derating (NEC 310.15(B)(1)) — assume 30 °C ambient.
- More than three current-carrying conductors in a raceway (NEC 310.15(C)(1)).
- Short-circuit current rating, fault duty or arc-flash analysis.
- Equipment grounding conductor sizing (NEC Table 250.122).
- Neutral conductor sizing for non-linear loads.
- Parallel runs (above 500 kcmil at single conductor).
Common mistakes & tips
- Use one-way distance, not loop length. The formula factor (2 for single-phase, √3 for three-phase) handles the round trip. Entering the loop length doubles the calculated drop.
- Pick the right temperature column. NEC 110.14(C)(1) requires the column matching the lowest-rated termination. Most residential breakers are 60 °C-rated for circuits ≤ 100 A; modern panels are 75 °C above 100 A.
- Mind the 240.4(D) small-conductor rule. Even if the 90 °C ampacity says #14 Cu can carry 25 A, the OCPD is capped at 15 A; #12 Cu at 20 A; #10 Cu at 30 A. The calculator flags this in the result note.
- Aluminum is bigger. Aluminum wire needs ~50 % more circular mils for the same ampacity. The K of 21.2 vs 12.9 means ~64 % more CM for the same voltage drop.
- Long runs are voltage-drop driven. For runs over 100 ft on small loads, voltage drop usually picks the wire size — not ampacity.
- Watch sub-panels and feeders. Feeder + branch combined drop is what reaches the load. Use 5 % combined or split between feeder (2 %) and branch (3 %).